The Fluke 707 and 705 Loop Calibrators are purpose-built for 4–20 mA loop and transmitter testing. Both models deliver 0.015 % mA accuracy on the 707 (0.02 % measure / 0.025 % source on the 705), 1 µA resolution, simultaneous mA and % of span display, and a 24 V internal loop supply — giving technicians a single, pocket-sized instrument for trimming, linearity checks, and loop troubleshooting.
Four things. Accuracy: the 707 is 0.015 % of reading on measure, source, and simulate; the 705 is 0.02 % on measure and 0.025 % on source and simulate. Interface: the 707 has the Quick Click rotary knob, the 705 uses push buttons. Drive capability: 1200 Ω on the 707 versus 1000 Ω at 24 mA on the 705. And HART mode, which only the 707 has. Everything else — 1 µA resolution, 25 % steps, ramps, span check, 24 V loop power, 28 V dc measurement, 9 V battery, three-year warranty — is on both.
No. HART mode switches a 250 Ω resistor into series with the 24 V loop supply so that a separate HART communicator can be clipped across the loop while the calibrator is connected. It does not read or write HART parameters, it has no HART modem and no device description library. If you need to configure a HART device, that is a 475 or a 709H, not a 707. This is the single most common misunderstanding about this model and it is worth one line of small print on your page.
No. Both instruments source and measure current (0–20 and 4–20 mA) and measure dc voltage up to 28 V. Neither sources voltage, and neither does frequency, resistance, thermocouples, or RTDs. If you need voltage sourcing or temperature, you are looking at the 715, 724, or 725, not the 705/707.
Only in the sense that it generates a 4–20 mA signal. It is not a general-purpose signal generator: no waveforms, no voltage output, no frequency. Calling it one on a global storefront attracts buyers looking for a function generator and produces returns.
Yes. In simulate mode the 707 and 705 present a variable resistance to the loop and need an external loop voltage of 12 to 30 V — typically the loop's own supply, or the calibrator's 24 V supply used in source mode instead. Source mode drives the loop from the internal 24 V and needs no external supply. Knowing which of the two modes you are in is the difference between a working test and a confusing one.
One 9 V alkaline cell, changed through a door that does not break the calibration seal. The data sheet's accessories line begins with a set of alligator-clip test leads and a 9 V alkaline battery, but the text available is cut off after that, so confirm the exact contents against your own box before publishing a "what's included" list — do not copy a competitor's list. Fluke does not publish a battery runtime figure for these models in the specification table.