Fluke 1732/1734 3-Phase Energy Logger for Energy Audits & Load Studies, 1500A Probes
| Capability | Fluke 1732 | Fluke 1734 |
|---|---|---|
| Load studies | Yes | Yes |
| Energy assessments / energy surveys | Yes | Yes |
| Trend recording | Yes | Yes |
| Fluke Connect wireless module support (up to 2 modules) | Upgrade package required | Included |
| Wi-Fi / Bluetooth | Optional | Included |
| Magnetic probe set (MP1, 4 pcs) | Optional | Included |
| Magnetic hanging strap | Optional | Included |
| 4th current channel (neutral current) | Not available | Not available |
| Harmonics measurement | Not available | Not available |
| Voltage event capture | Not available | Not available |
| EN 50160 PQ health overview | Not available | Not available |
| Parameter | Range | Max. resolution | Accuracy (reading + full scale) |
|---|---|---|---|
| Voltage | 1000 V | 0.1 V | ±(0.2 % + 0.01 %) |
| Current — i17xx-flex1500 12 in | 150 A / 1500 A | 0.1 A / 1 A | ±(1 % + 0.02 %) |
| Current — i17xx-flex3000 24 in (optional) | 300 A / 3000 A | 1 A / 10 A | ±(1 % + 0.03 %) |
| Current — i17xx-flex6000 36 in (optional) | 600 A / 6000 A | 1 A / 10 A | ±(1.5 % + 0.03 %) |
| Current — i40s-EL 40 A clamp (optional) | 4 A / 40 A | 1 mA / 10 mA | ±(0.7 % + 0.02 %) |
| Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1 %) |
| Auxiliary input | ±10 V dc | 0.1 mV | ±(0.2 % + 0.02 %) |
| Voltage min / max | 1000 V | 0.1 V | ±(1 % + 0.1 %) |
| Current min / max | Defined by accessory | Defined by accessory | ±(5 % + 0.2 %) |
| THD on voltage | 1000 % | 0.1 % | ±0.5 |
| THD on current | 1000 % | 0.1 % | ±0.5 |
Instrument, power supply, voltage test leads, alligator clips (4), i17xx-flex1500 12 in flexible current probes (3), C173x soft case, Energy Analyze Plus software, line cords, colour coding set, documentation on USB flash drive.
The same contents plus the 173x magnetic hanging strap and MP1 magnet probe set (4).
Start at the main service feeder and log power and energy for a period that matches a normal operating cycle — a seven-day run for a five-day facility, or a single day if the load is constant 24/7/365. Compare the logged kWh against the utility meter to confirm you are being billed correctly, then move downstream to the largest loads identified by panel current rating.
Quantify what a machine actually draws at minimum and maximum capacity, and confirm circuit capacity before adding another load. The data set supports NEC 220.87 load calculations used in the United States. Thirty days is the usual recommendation so that all typical load conditions occur during the test.
Establish the baseline consumption of a chiller, compressor bank, air handler or production line, install the improvement, then re-log under the same conditions. The difference is the documented saving, which is what justifies the project internally.
Utilities bill more than kWh — peak demand over a 15 or 30 minute window and power factor penalties both show up on the invoice. The 1732/1734 characterise both, so you can see whether a capacitor bank is switching correctly or whether a demand spike is a single motor start.
Where a voltage connection is impractical, the simplified load study feature logs current alone and uses an entered nominal voltage to produce a simulated power profile. Useful for a quick survey on a live busbar you cannot shut down.
Two auxiliary inputs accept 0 to ±10 V dc from any transducer, and the 1734 adds two Fluke Connect wireless inputs. Log temperature, pressure or flow on the same time base as kW and you can see whether an energy spike tracks a process condition or a fault.
Plant maintenance teams, ESCOs, energy consultants, HVAC commissioning engineers, and electrical contractors performing power quality and energy work for commercial buildings.
Both instruments use the same measurement engine, the same four voltage and three current inputs, the same accuracy and the same 4.3 in touch screen. The 1734 adds three things: built-in Wi-Fi and Bluetooth, the magnetic hanging strap and MP1 magnet probe set, and support for up to two Fluke Connect wireless modules so extra parameters are logged alongside the power data. Both versions ship with the three flexible current probes in the /INTL and /EUS configurations. Choose the 1734 if you want to log temperature or pressure simultaneously or stream data without a USB stick; choose the 1732 if you only need power and energy and will download by USB. Note that a 1732 can be upgraded to 1734 capability with a Fluke upgrade package, but neither model can be upgraded to 1736/1738 power-logger functions.
No. The 1732 and 1734 are energy loggers: they log RMS voltage, RMS current, THD, active/reactive/apparent power, power factor and energy. Harmonic spectrum analysis, individual harmonic limits, EN 50160 PQ health reporting, a fourth neutral-current channel and voltage event capture belong to the 1736 and 1738 Power Loggers. If your customer needs a compliance-grade power quality study to EN 50160 or IEEE 519, this is the wrong model and the 1738 is the right one. Publishing the 1732/1734 as a "power quality analyser" without that limitation is the single most common source of "item not as described" disputes on this family.
Neither. The detachable power supply takes 100 V to 500 V directly from the circuit being measured, through the same voltage leads, so the logger powers itself from the panel it is logging. It can also run from any 100 V to 240 V outlet using an IEC 60320 C7 cord if one is available. The instrument has no internal battery for logging, so it must remain powered for the duration of the session.
1-phase, 1-phase IT, split phase, 3-phase delta, 3-phase wye, 3-phase wye IT, 3-phase wye balanced, 3-phase Aron/Blondel two-element delta, 3-phase delta open leg, plus a current-only mode for simplified load studies. The instrument detects and scales the attached probes automatically, and the Verify Connection screen flags a reversed current direction, a swapped phase or a missing voltage reference before you walk away from the panel.
Internal flash holds more than 20 separate logging sessions with capacity for over a year of continuous data — the practical limit is usually the survey design, not the memory. Sessions can be reviewed on screen while logging continues. Download to a USB flash drive in the field, pull the files over Wi-Fi, or connect USB mini-B to a PC and open them in Energy Analyze Plus, which compares parameters across sessions and generates the report automatically.
The /INTL package includes the instrument, detachable power supply, voltage test leads, four alligator clips, three 12 in 1500 A flexible current probes, soft carry case, colour coding set, line cords, USB flash drive with documentation, and the Energy Analyze Plus software. The 1734 adds the magnetic hanging strap and four MP1 magnet probes. Fluke's documentation lists the Wi-Fi/Bluetooth adapter as included on the /EUS and /WINTL variants and optional on /INTL, so confirm the adapter content with us before ordering if wireless transfer is a requirement — we will tell you exactly what is in the case rather than let you find out after delivery.