Shanghai Fradwell Industrial Automation Co., Ltd. 86-21-68060766 cnsales@fradwell.com
Fluke 1732/1734 3-Phase Energy Logger for Energy Audits & Load Studies, 1500A Probes

Fluke 1732/1734 3-Phase Energy Logger for Energy Audits & Load Studies, 1500A Probes

  • Highlight

    3-phase energy logger with 1500A probes

    ,

    Fluke 1732/1734 energy audit logger

    ,

    load study power logger

  • Logging Channels
    4 Voltage (3-phase + Neutral) + 3 Current, Simultaneous
  • Max Voltage Rating
    1000 V CAT III / 600 V CAT IV
  • Included Current Probe Range
    3 × I17xx-flex1500 12 In, 1–150 A / 10–1500 A Ac
  • Supported Circuit Types
    1-phase, Split Phase, 3-phase Delta / Wye / Wye IT / Aron-Blondel, Current-only
  • Connectivity
    USB-A, USB Mini-B, Wi-Fi, Bluetooth (Fluke Connect)
  • Measurement Scope
    Energy And Load Logging — No Harmonic Spectrum Analysis, No Voltage Event Capture
  • Shipping Term
    International Express(DHL/FEDEX/TNT/UPS/ARAMEX)/Sea Freight / Air Freight / International Special Line
  • Freight Charge
    For Industrial Equipment (E.G., PLC Modules, Inverters..), Shipping Cost Varies By Package Weight/Volume And Delivery Location. Contact Our Sales Team For A Customized Shipping Solution And Quot
  • Brand Name
    Fluke
  • Model Number
    Fluke 1732/1734
  • Minimum Order Quantity
    1
  • Price
    $4800 - $6800
  • Packaging Details
    Original
  • Delivery Time
    3-5Workdays
  • Payment Terms
    L/C,D/A,D/P,T/T

Fluke 1732/1734 3-Phase Energy Logger for Energy Audits & Load Studies, 1500A Probes

Product Highlights

Fluke 1732/1734 3-Phase Energy Logger for Energy Audits & Load Studies, 1500A Probes

  • Logs the whole circuit, automatically. RMS voltage, RMS current, voltage and current THD, active power, reactive power, apparent power, power factor, active energy and reactive energy are all captured simultaneously. Every available parameter is selected automatically when the session starts, so you are not left guessing which channel you should have enabled.
  • Three-phase in one setup. Four voltage inputs (L1, L2, L3, N) and three current inputs, with the three included i17xx-flex1500 12 in flexible probes auto-detected and auto-scaled by the instrument. Each probe switches between a 150 A and a 1500 A range, so one probe set covers a 16 A branch circuit and a 1500 A service feeder.
  • Highest safety rating in its class. 600 V CAT IV / 1000 V CAT III — rated for connection at the service entrance and everywhere downstream, not just at the branch panel.
  • Powers itself from the circuit it is measuring. The detachable power supply accepts 100 V to 500 V from the measurement circuit, or 100 V to 240 V through a standard IEC 60320 C7 cord. No hunting for an outlet, no extension cords across the plant floor.
  • Guided setup with digital correction. The intelligent Verify Connection function checks phase mapping and current direction, then digitally corrects most common misconnections — reversed CT polarity, swapped phases — without asking you to disconnect and rewire the leads.
  • 4.3 in colour touch screen. 480 × 272 active-matrix TFT with resistive touch, so you can review trends, run calculations and check data on site before you ever download it.
  • More than 20 sessions, more than a year of data. Internal flash storage holds over 20 separate logging sessions and enough data for more than a year of continuous logging. Sessions can be reviewed while logging is still in progress.
  • Download without a laptop. Copy files straight to a USB flash drive in the instrument's USB-A port, or transfer over Wi-Fi. No need to bring a computer to the panel or return to the workshop.
  • Energy Analyze Plus software included. Compare any measured parameter across sessions, build automated reports, and quantify savings before and after a retrofit.
  • 1734 adds Fluke Connect. The 1734 supports up to two Fluke Connect wireless modules, so temperature, pressure or any other module parameter is logged on the same time base as the power data. The 1732 can be upgraded to this later with a Fluke upgrade package.
Model Comparison: Fluke 1732 vs. Fluke 1734
Capability Fluke 1732 Fluke 1734
Load studiesYesYes
Energy assessments / energy surveysYesYes
Trend recordingYesYes
Fluke Connect wireless module support (up to 2 modules)Upgrade package requiredIncluded
Wi-Fi / BluetoothOptionalIncluded
Magnetic probe set (MP1, 4 pcs)OptionalIncluded
Magnetic hanging strapOptionalIncluded
4th current channel (neutral current)Not availableNot available
Harmonics measurementNot availableNot available
Voltage event captureNot availableNot available
EN 50160 PQ health overviewNot availableNot available
Technical Specifications
Parameter Range Max. resolution Accuracy (reading + full scale)
Voltage1000 V0.1 V±(0.2 % + 0.01 %)
Current — i17xx-flex1500 12 in150 A / 1500 A0.1 A / 1 A±(1 % + 0.02 %)
Current — i17xx-flex3000 24 in (optional)300 A / 3000 A1 A / 10 A±(1 % + 0.03 %)
Current — i17xx-flex6000 36 in (optional)600 A / 6000 A1 A / 10 A±(1.5 % + 0.03 %)
Current — i40s-EL 40 A clamp (optional)4 A / 40 A1 mA / 10 mA±(0.7 % + 0.02 %)
Frequency42.5 Hz to 69 Hz0.01 Hz±(0.1 %)
Auxiliary input±10 V dc0.1 mV±(0.2 % + 0.02 %)
Voltage min / max1000 V0.1 V±(1 % + 0.1 %)
Current min / maxDefined by accessoryDefined by accessory±(5 % + 0.2 %)
THD on voltage1000 %0.1 %±0.5
THD on current1000 %0.1 %±0.5
What's in the Box
FLUKE-1732/INTL

Instrument, power supply, voltage test leads, alligator clips (4), i17xx-flex1500 12 in flexible current probes (3), C173x soft case, Energy Analyze Plus software, line cords, colour coding set, documentation on USB flash drive.

FLUKE-1734/INTL

The same contents plus the 173x magnetic hanging strap and MP1 magnet probe set (4).

Note on variants: Probe-inclusive /INTL and /EUS versions ship with the three flexible probes. The /B versions do not include current probes. The Wi-Fi/Bluetooth adapter is bundled with the /EUS and /WINTL versions and listed as optional on the /INTL versions — confirm the exact adapter content of your unit before publishing.
Applications
Energy surveys and utility bill verification

Start at the main service feeder and log power and energy for a period that matches a normal operating cycle — a seven-day run for a five-day facility, or a single day if the load is constant 24/7/365. Compare the logged kWh against the utility meter to confirm you are being billed correctly, then move downstream to the largest loads identified by panel current rating.

Load studies before adding capacity

Quantify what a machine actually draws at minimum and maximum capacity, and confirm circuit capacity before adding another load. The data set supports NEC 220.87 load calculations used in the United States. Thirty days is the usual recommendation so that all typical load conditions occur during the test.

Energy assessments before and after a retrofit

Establish the baseline consumption of a chiller, compressor bank, air handler or production line, install the improvement, then re-log under the same conditions. The difference is the documented saving, which is what justifies the project internally.

Peak demand and power factor investigation

Utilities bill more than kWh — peak demand over a 15 or 30 minute window and power factor penalties both show up on the invoice. The 1732/1734 characterise both, so you can see whether a capacitor bank is switching correctly or whether a demand spike is a single motor start.

Simplified current-only load studies

Where a voltage connection is impractical, the simplified load study feature logs current alone and uses an entered nominal voltage to produce a simulated power profile. Useful for a quick survey on a live busbar you cannot shut down.

Correlating power with process conditions

Two auxiliary inputs accept 0 to ±10 V dc from any transducer, and the 1734 adds two Fluke Connect wireless inputs. Log temperature, pressure or flow on the same time base as kW and you can see whether an energy spike tracks a process condition or a fault.

Facilities, manufacturing and service use

Plant maintenance teams, ESCOs, energy consultants, HVAC commissioning engineers, and electrical contractors performing power quality and energy work for commercial buildings.

Frequently Asked Questions
Q1. What is the actual difference between the Fluke 1732 and the Fluke 1734?

Both instruments use the same measurement engine, the same four voltage and three current inputs, the same accuracy and the same 4.3 in touch screen. The 1734 adds three things: built-in Wi-Fi and Bluetooth, the magnetic hanging strap and MP1 magnet probe set, and support for up to two Fluke Connect wireless modules so extra parameters are logged alongside the power data. Both versions ship with the three flexible current probes in the /INTL and /EUS configurations. Choose the 1734 if you want to log temperature or pressure simultaneously or stream data without a USB stick; choose the 1732 if you only need power and energy and will download by USB. Note that a 1732 can be upgraded to 1734 capability with a Fluke upgrade package, but neither model can be upgraded to 1736/1738 power-logger functions.

Q2. Does it measure harmonics and capture voltage events like a power quality analyser?

No. The 1732 and 1734 are energy loggers: they log RMS voltage, RMS current, THD, active/reactive/apparent power, power factor and energy. Harmonic spectrum analysis, individual harmonic limits, EN 50160 PQ health reporting, a fourth neutral-current channel and voltage event capture belong to the 1736 and 1738 Power Loggers. If your customer needs a compliance-grade power quality study to EN 50160 or IEEE 519, this is the wrong model and the 1738 is the right one. Publishing the 1732/1734 as a "power quality analyser" without that limitation is the single most common source of "item not as described" disputes on this family.

Q3. Do I need to shut down the panel or find a power outlet to run it?

Neither. The detachable power supply takes 100 V to 500 V directly from the circuit being measured, through the same voltage leads, so the logger powers itself from the panel it is logging. It can also run from any 100 V to 240 V outlet using an IEC 60320 C7 cord if one is available. The instrument has no internal battery for logging, so it must remain powered for the duration of the session.

Q4. What circuit configurations are supported?

1-phase, 1-phase IT, split phase, 3-phase delta, 3-phase wye, 3-phase wye IT, 3-phase wye balanced, 3-phase Aron/Blondel two-element delta, 3-phase delta open leg, plus a current-only mode for simplified load studies. The instrument detects and scales the attached probes automatically, and the Verify Connection screen flags a reversed current direction, a swapped phase or a missing voltage reference before you walk away from the panel.

Q5. How long can it log, and how do I get the data out?

Internal flash holds more than 20 separate logging sessions with capacity for over a year of continuous data — the practical limit is usually the survey design, not the memory. Sessions can be reviewed on screen while logging continues. Download to a USB flash drive in the field, pull the files over Wi-Fi, or connect USB mini-B to a PC and open them in Energy Analyze Plus, which compares parameters across sessions and generates the report automatically.

Q6. What is included, and does my unit include the Wi-Fi/Bluetooth adapter?

The /INTL package includes the instrument, detachable power supply, voltage test leads, four alligator clips, three 12 in 1500 A flexible current probes, soft carry case, colour coding set, line cords, USB flash drive with documentation, and the Energy Analyze Plus software. The 1734 adds the magnetic hanging strap and four MP1 magnet probes. Fluke's documentation lists the Wi-Fi/Bluetooth adapter as included on the /EUS and /WINTL variants and optional on /INTL, so confirm the adapter content with us before ordering if wireless transfer is a requirement — we will tell you exactly what is in the case rather than let you find out after delivery.