| Function | Range | Resolution | Accuracy |
|---|---|---|---|
| Air pressure | ±4000 Pa / ±16 in H₂O / ±400 mm H₂O / ±40 mbar / ±0.6 PSI | 1 Pa / 0.001 in H₂O / 0.1 mm H₂O / 0.01 mbar / 0.0001 PSI | ±1 % + 1 Pa / ±1 % + 0.01 in H₂O / ±1 % + 0.1 mm H₂O / ±1 % + 0.01 mbar / ±1 % + 0.0001 PSI |
| Air velocity | 1 to 80 m/s (250 to 16,000 fpm) | 0.001 m/s (1 fpm) | ±2.5 % of reading at 2000 fpm (10.00 m/s) |
| Air flow | 0 to 99,999 cfm / m³/hr / l/s | 1 cfm / 1 m³/hr / 1 l/s | Function of velocity and duct size |
| Temperature | 0 °C to 50 °C (32 °F to 122 °F) | 0.1 °C / 0.1 °F | ±1 % + 2 °C (±1 % + 4 °F) |
| Parameter | Fluke 922 | Fluke 922/KIT |
|---|---|---|
| Measurement | ||
| Air pressure range | ±4000 Pa (±16 in H₂O / ±40 mbar) | ±4000 Pa (±16 in H₂O / ±40 mbar) |
| Pressure resolution | 1 Pa | 1 Pa |
| Pressure accuracy | ±1 % + 1 Pa | ±1 % + 1 Pa |
| Air velocity range | 1 to 80 m/s (250 to 16,000 fpm) | 1 to 80 m/s (250 to 16,000 fpm) |
| Velocity resolution | 0.001 m/s | 0.001 m/s |
| Velocity accuracy | ±2.5 % of reading at 10.00 m/s | ±2.5 % of reading at 10.00 m/s |
| Air flow range | 0 to 99,999 cfm / m³/hr / l/s | 0 to 99,999 cfm / m³/hr / l/s |
| Temperature range | 0 to 50 °C (32 to 122 °F) | 0 to 50 °C (32 to 122 °F) |
| Temperature accuracy | ±1 % + 2 °C | ±1 % + 2 °C |
| Instrument | ||
| Ingress protection | IP40 | IP40 |
| Stored readings | 99 | 99 |
| Power and battery life | 4 × AA, 375 h (80 h with backlight) | 4 × AA, 375 h (80 h with backlight) |
| Warranty | 2 years | 2 years |
| Package Contents | ||
| 12 in pitot tube | Not included | Included |
| ToolPak hanger | Not included | Included |
| Two rubber hoses | Included | Included |
| Wrist strap | Included | Included |
| Four AA batteries | Included | Included |
| User's manual | Included | Included |
| Carrying case | Soft case | Hard case |
| Optional add-on | PT12 pitot tube, 12 in | — |
| Feature | Fluke 922 / 922 KIT | Fluke 923 |
|---|---|---|
| Sensing principle | Pitot tube on a pressure port | Hot-wire thermal probe |
| Velocity range | 1 to 80 m/s | 0.20 to 20.00 m/s |
| Pressure measurement | Yes, ±4000 Pa differential and static | No — barometric pressure is an entered setting only |
| Temperature range | 0 to 50 °C | −20 to 60 °C |
| Stored readings | 99 | 198 (99 velocity + 99 flow) |
| Ingress protection | IP40 | Not stated |
| Best at | Duct traverses, filter and coil drop, building pressure | Low-speed air at grilles, hoods and cleanroom FFUs |
Buy the 922 if the job involves pressure. Buy the 923 if it involves slow air in tight spaces. These are different instruments, not trim levels. The 922 is a micromanometer that derives velocity from a pitot tube, so it also reads differential and static pressure — which is what filter drop, coil drop and room pressurisation work actually requires. The 923 is a hot-wire anemometer: it reads from 0.20 m/s and its slim probe fits grilles and FFU faces, but it has no pressure sensor at all. Many contractors end up with both, because neither covers the other's job.
No — velocity comes from the pitot tube. The meter measures pressure at its ports; velocity is calculated from the velocity pressure the pitot generates. That is why the /KIT version exists: it bundles the 12 in pitot tube, the ToolPak hanger and a hard case, so the instrument is usable the day it arrives. Buying the bare 922 and sourcing a pitot separately is possible — it is compatible with most pitot tubes — but you will still need the hoses and somewhere to store them.
Fluke states it as a function of velocity and duct size, not a single percentage. That is not evasion — flow is velocity multiplied by cross-sectional area, so any error in your duct measurement propagates straight into the flow figure. It is why the meter asks you to enter duct shape and dimensions rather than assuming a round duct. Enter the real dimensions and the flow number is only as good as your tape measure and your traverse.
Yes — ±4000 Pa is comfortable for that. Typical building pressure targets sit in the tens of pascals, and severe stack-effect or fan-driven cases rarely exceed a few hundred pascals. The 1 Pa resolution matters more than the range here, and the bi-directional channel means a reversed reading shows as a negative number rather than needing the hoses swapped.
Four AA cells. 375 hours without the backlight, 80 hours with it. The backlight cuts runtime by roughly four-fifths, which is worth knowing before a long commissioning week — use it only when the plant room is actually dark. Auto power off is included.
IP40, EMC to EN 61326-1, MIL-PREF-28800F Class 3 vibration, two-year warranty. IP40 means protection against solid objects over 1 mm and no liquid protection — this is an indoor instrument, so do not leave it in the rain or on a wet roof. The datasheet states EN 61326-1 EMC conformance.