1. First, What Problem Does a Soft Starter Actually Solve?

Direct-on-line (DOL) starting is the simplest and cheapest option, but it costs you in two places:

  • Current surge: inrush current can reach several times the rated current (industry-common value: commonly quoted in the 6–8× rated current range; the actual multiple depends on motor design), causing grid voltage dips that can trip other equipment on the same supply;
  • Mechanical shock: full-voltage starting produces an abrupt torque step — extra stress on belts, gears, couplings, and piping (water hammer in pumps).

How a soft starter handles this: per Eaton's official technical article, a soft starter is a solid-state device that protects AC motors from damage caused by sudden power influx by limiting the large initial inrush current associated with motor startup. It provides a gentle ramp up to full speed and is used only at startup (and stop, if equipped), achieved by ramping up the voltage applied to the motor.

How it is implemented (per Eaton): most soft starters use thyristors or silicon controlled rectifiers (SCRs) in series to reduce voltage. The SCRs are engaged during ramp-up, and bypass contactors are pulled in after maximum speed is achieved, which significantly reduces motor heating. The formal name is RVSS — reduced voltage soft starter.

2. Soft Starter vs VFD: How to Choose
2.1 The one-line test

Do you need variable speed during the run phase?

  • No variable speed needed (soft start/stop only) → soft starter;
  • Variable speed, process control, or energy savings needed → VFD.
2.2 Official application guidance (per Eaton's official technical article)

Choose a VFD when:

  • Complete speed control is required;
  • Energy savings is a goal;
  • Custom control is needed.

Choose a soft starter when:

  • Speed and torque control are required only during startup (and stop, if equipped with soft stop);
  • You need to reduce the large startup inrush current of a large motor;
  • The mechanical system requires a gentle start to relieve torque spikes and tension during normal startup (e.g. conveyors, belt-driven systems, gears);
  • Pumps are used to eliminate pressure surges caused in piping systems when fluid changes direction rapidly (water hammer).
2.3 Technical comparison
Dimension Soft starter VFD
Speed control during run Not available (after bypass, equivalent to DOL) Available, continuous across the whole cycle
Starting current control Voltage reduction / current limit (adjustable) Current and torque controlled from near-zero speed
Rated torque at zero/low speed No Yes (with vector control)
Harmonics / power quality Limited harmonics during start; negligible after bypass Rectifier + inverter topology, usually needs line reactors/filters for harmonic mitigation
Energy savings None (not in circuit during run) Significant: Eaton states up to ~50% savings in US/Canada markets; under the affinity laws for fans, flow varies linearly with speed, pressure with the square, and power with the cube of speed
Footprint / cabinet space More compact (especially at higher power) Larger (especially at higher power)
Upfront cost Lower Eaton: typically 2-3× the cost of a soft starter
Life-cycle cost Low upfront cost, no runtime energy benefit Higher upfront cost, offset by savings on variable-speed duty
2.4 Decision checklist

Choose a soft starter if:

  1.  The motor runs at fixed speed and the process needs no speed variation;
  2.  You only need to eliminate starting current surge / grid voltage dip / mechanical shock;
  3.  Starting is infrequent (soft starters typically have a starts-per-hour limit — always check the datasheet);
  4.  Cabinet space is tight, or budget is sensitive at higher power ratings;
  5.  The load is a fan, pump (soft start/stop only), conveyor, or compressor at fixed speed.

You must choose a VFD if:

  1.  The process needs variable speed (flow / pressure / tension / line-speed closed loop);
  2.  The goal is energy savings (greatest for centrifugal fans and pumps);
  3.  Rated torque is needed at zero or very low speed (hoisting, winding, extrusion);
  4.  You need S-curves, positioning, or multi-drive synchronization;
  5.  Starting is frequent, or jogging is required (soft starters are not suited to high-cycle duty).
3. Three-Brand Specification Comparison 
3.1 ABB PSR Series (Compact)

Positioning: entry-level/compact, focused on small footprint and integrated bypass.

  • Current range: rated operational current 3.9–105 A (UL max FLA 3.4–104 A), per-model from PSR3 (3.9 A) to PSR105 (105 A) (per ABB PSR datasheet);
  • Power range: 1.5–55 kW at 400 V; 0.75–30 kW at 230 V; 2.2–55 kW at 500 V (per official datasheet); UL horsepower 2–75 hp at 440–480 V and 2–100 hp at 550–600 V;
  • Bypass: built-in on all sizes (datasheet wording: "Built-in by-pass on all sizes");
  • Voltage: rated operational voltage 208–600 V AC (+10%/−15%); control supply 100–240 V AC or 24 V AC/DC;
  • Protection rating: IP20 (whole range);
  • Communication: no built-in communication; ABB FieldBusPlug option supports Profibus, Modbus, DeviceNet, CANopen;
  • Protection: no electronic motor overload protection in the device body. The datasheet pairs it with external thermal overload relays (TF42/TF65/TF96/TF140DU); short-circuit and overload protection is provided by manual motor starters (MS116/MS132, etc.) or gG fuses. Run and top-of-ramp (TOR) signal relays are built in;
  • Other: starting capability 4 × Ie / 6 s; start ramp 1–20 s, stop ramp 0–20 s; initial/final voltage 40–70%; operating temperature −25…+60 °C (derating above 40 °C); PSR3–PSR45 support DIN-rail mounting (per official datasheet);
  • Representative models: PSR30-600-70 (30 A / 15 kW @400 V); PSR45-600-70 (45 A / 22 kW @400 V); PSR105-600-70 (105 A / 55 kW @400 V).
3.2 Schneider Altistart 48 (ATS48) — Discontinued, Mind the Replacement

Critical status (per Schneider official datasheet): ATS48 is discontinued (Discontinued on: 2023-07-12), with the datasheet listing end-of-service on 2030-12-31. The official replacement range is Altistart 480 (ATS480). Spare-part sourcing, legacy replacement, and new projects should move to ATS480.

Verified representative model specifications:

Model Rated current Power range Voltage range
ATS48D17Q 14.8 A 3–15 kW 230…415 V
ATS48C25Y 240 A 55–250 kW 208…690 V
  • Bypass: no built-in bypass — datasheet field reads "External bypass (optional)";
  • Utilization category: AC-53A; positioned as "Heavy duty industry and pumps";
  • Protection: phase failure (line side), motor thermal protection, starter thermal protection; inputs include a PTC thermistor input (750 Ω @25 °C);
  • Communication: built-in Modbus (1 × RJ45, RS485 multidrop serial, 4800/9600/19200 bps);
  • Certifications and standards: CE marking; certifications include UL, CCC, GOST, DNV, CSA and more; standard EN/IEC 60947-4-2 (EMC also references that standard and the IEC 61000-4 series);
  • Environment: operating temperature −10…40 °C without derating, derating 2% per °C from 40…60 °C; altitude 1000–2000 m derating 2.2% per 100 m.

In one line: built-in Modbus plus onboard thermal protection are its differentiators — but it is discontinued, so evaluate ATS480 directly for new projects.

3.3 Siemens SIRIUS 3RW (3RW5 Generation; 3RW52 Data Verified)

Product structure (per Siemens official SIOS page): the 3RW5 generation has three tiers — 3RW50 (Basic) / 3RW52 (General Performance) / 3RW55 (High Performance; plus the 3RW55 Failsafe safety version). The previous generation is 3RW44 (high feature/performance).

Verified 3RW52 specifications:

  • Power range: 5.5–560 kW (at 400 V) (Siemens catalogue wording);
  • Current range: rated operational current 13–570 A, per model from 3RW5213 (13 A) to 3RW5248 (570 A);
  • Voltage: two versions — 200–480 V or 200–600 V (−15/+10%); control supply 24 V AC/DC or 110–250 V AC;
  • Protection rating: IP20 on smaller sizes, IP00 on some models from 3RW5224 upward; optional IP65 door-mounting kit;
  • Protection: motor protection trip classes selectable per IEC 60947-4-2 — CLASS 10A / 10E / 20E (including 20E for heavy-duty starting);
  • Communication: optional plug-in communication modules — PROFINET, PROFIBUS, EtherNet/IP, and Modbus (both TCP and RTU); optional HMI module; configuration and diagnostics via SIRIUS Soft Starter ES (TIA Portal);
  • Certifications: CE, UL, EAC;
  • Other: Soft Torque function (reduces mechanical load, optimizes pump stopping); maximum cable length between soft starter and motor 800 m; operating temperature −25…+60 °C; installation altitude up to 5000 m.

In one line: widest power coverage (to 560 kW), the richest communication options (optional native PROFINET), and protection classes selectable for heavy-duty starting — suited to mid-to-large machines that must join an automation network.

3.4 Side-by-Side Comparison
Item ABB PSR Schneider ATS48 Siemens 3RW5 (3RW52)
Positioning Compact entry-level (smallest footprint) Heavy-duty industry and pumps (high-end) 3RW50 Basic / 3RW52 General / 3RW55 High Performance & Failsafe
Status Active Discontinued (2023-07-12) → ATS480 Active
Current coverage 3.9–105 A 14.8–240 A (verified model points) 13–570 A
Power coverage 1.5–55 kW @400 V 3–250 kW (verified model points) 5.5–560 kW @400 V
Built-in bypass Built-in on all sizes None built-in; external bypass optional Hybrid switching technology (confirm per model)
Motor overload protection Requires external thermal overload relay Onboard (motor + starter thermal protection) Onboard, selectable CLASS 10A/10E/20E
Communication FieldBusPlug option (Profibus/Modbus/DeviceNet/CANopen) Built-in Modbus Optional PROFINET / PROFIBUS / EtherNet/IP / Modbus modules
Protection rating IP20 Not listed in datasheet (confirm in official manual) IP20 / IP00; optional IP65 door-mounting kit
Best fit Low power, tight cabinet space, cost-sensitive Legacy ATS48 replacement (move to ATS480), pump duty Mid-to-large power, lines that must join PROFINET and similar networks
4. Field Selection Checklist

Step 1 — Determine the starting method

  • Is variable speed needed during run? Yes → VFD, stop here. No → continue;

Step 2 — Set the duty class from the load type

  • Load type: light duty (fans, centrifugal pumps) / heavy duty (conveyors, crushers, mixers, compressors starting under load);
  • Heavy-duty starting must be selected by duty class (Siemens 3RW52 offers CLASS 20E for heavy duty; Schneider ATS48 selections use utilization category AC-53A and heavy-duty power points).Do not match the motor's nominal power directly to the device rating;

Step 3 — Check starts per hour

  • Record starts per hour and duration per start, and compare with the datasheet's starts-per-hour table / starting capability (e.g. ABB PSR: 4 × Ie / 6 s). For high-cycle duty, consider a VFD instead;

Step 4 — Check bypass configuration and cabinet space

  • Built-in bypass (ABB PSR) → saves a contactor and wiring in the cabinet;
  • External bypass (ATS48 optional) → reserve space and budget for the bypass contactor;
  • At higher power, soft starters generally save cabinet space versus an equivalent VFD (per Eaton's official comparison);

Step 5 — Check protection configuration (the most commonly missed item)

  • Does the device include motor overload protection? ABB PSRdoes not— add TF-series thermal overload relays plus short-circuit protection; ATS48 and 3RW52 can be configured onboard;
  • Is a PTC/thermistor input needed? (ATS48 provides one)

Step 6 — Check communication and integration

  • Will it connect to a PLC/SCADA? Budget separately for built-in Modbus (ATS48), the FieldBusPlug option (ABB PSR), or plug-in modules (Siemens, optional PROFINET);

Step 7 — Check environment and derating

  • Cabinet temperature, altitude, mounting clearances — all three brands publish explicit derating rules (e.g. ABB PSR derates 0.8% per °C above 40 °C; ATS48 derates 2% per °C from 40–60 °C);

Step 8 — Check lifecycle and spares

  • Are you specifying a discontinued model? (ATS48 is discontinued — move to ATS480);
  • Do spares and support coverage match your line's service life?


5. Field Pitfalls

The following are common issues observed on projects, not statistical conclusions.

  • Pitfall 1: Buying the soft starter as an all-in-one "starting + protection" unit. The ABB PSR body has no electronic motor overload protection (per official datasheet) and requires external TF-series thermal overload relays. Miss this in the quotation and you are adding hardware on site (single-project example, not a statistical conclusion).
  • Pitfall 2: Assuming a soft starter saves energy. Once the bypass closes, the soft starter no longer participates in running, and the run phase equals DOL (per Eaton's official explanation) — there is no runtime energy saving. If electricity cost is a KPI, specify a VFD.
  • Pitfall 3: Ignoring bypass configuration and having to rebuild the cabinet. Built-in bypass (PSR) versus optional external bypass (ATS48) changes cabinet layout, contactor count, and cost completely. Designing the cabinet on the assumption that "a bypass exists either way" is more expensive to fix than to get right.
  • Pitfall 4: Selecting heavy-duty starting by nominal power. Conveyors, crushers, and mixers need far more starting torque than fans and pumps. Matching the motor nameplate power directly results in failed starts or repeated tripping; select one step up by duty class (e.g. CLASS 20E / heavy-duty power point).
  • Pitfall 5: Overlooking the starts-per-hour limit. Soft starters have starting capability limits (e.g. ABB PSR: 4 × Ie / 6 s, with a starts-per-hour table in the datasheet). High-cycle duty (a dozen starts per hour) calls for a VFD.
  • Pitfall 6: Specifying a discontinued model. Schneider ATS48 was discontinued on 2023-07-12 (replaced by ATS480); procuring against an old drawing risks lead-time, spare-part, and long-term support problems (the datasheet notes end-of-service on 2030-12-31).
6. Product Tie-in: Soft Starter Sourcing

Fradwell distributes the following soft starter brands with worldwide shipping and selection support:

  • ABB PSR series (3.9–105 A / 1.5–55 kW @400 V, built-in bypass on all sizes):https://mao.ecer.com/test/industrial-automationcontrol.com/sale-55897299-abb-pst-series-standard-soft-starter-3-phase-motor-controller-for-pumping-station-fan.html;
  • Schneider Altistart series (including legacy ATS48 replacement options and ATS480 for new projects):https://mao.ecer.com/test/industrial-automationcontrol.com/sale-55390042-schneider-altistart-480-ats480-ats22-soft-starter-17a-1200a-motor-control-new.html;
  • Siemens SIRIUS 3RW series (3RW50 / 3RW52 / 3RW55):https://mao.ecer.com/test/industrial-automationcontrol.com/sale-55385543-siemens-sirius-3rw52-3rw55-3rw40-soft-starter-motor-controller-original-new.html.

Selection support: send us the motor nameplate (power, current, speed), load type, starting frequency, cabinet temperature, and whether network integration is required — we will come back with a comparison recommendation.


7. Conclusion

Soft starters and VFDs are not substitutes; they divide the work. A soft starter addresses starting current and mechanical shock; a VFD addresses runtime speed control and energy savings.

Three tests, in priority order:

  1. Variable speed during run? If yes, choose a VFD;
  2. Energy savings required? If yes, choose a VFD (greatest benefit on centrifugal fans and pumps);
  3. Only need to limit starting shock, with infrequent starts? Then a soft starter is more compact and more economical (a VFD costs roughly 2-3× more up front).

By brand: for compact low-power duty look at ABB PSR (built-in bypass on all sizes); for pump duty and legacy replacement look at Schneider (ATS48 discontinued, move to ATS480); for mid-to-large power with PROFINET-class integration look at Siemens 3RW5.


FAQ

Q1: Does a soft starter save energy? No. A soft starter works only during starting by reducing voltage to limit current; once maximum speed is reached the bypass contactor closes and the run phase is the same as DOL (per Eaton's official explanation). For energy savings, specify a VFD.

Q2: Which is better, a soft starter or a VFD? They serve different purposes. Variable speed during run, energy savings, or rated torque at zero speed → VFD. Fixed-speed duty where you only need to limit starting current and mechanical shock → soft starter (more compact, lower upfront cost). Per Eaton's official technical article, a VFD typically costs 2-3× more than a soft starter up front.

Q3: Does a soft starter need a bypass? Yes, but the form differs: ABB PSR has built-in bypass on all sizes; Schneider ATS48 has no built-in bypass, with external bypass available as an option. Built-in bypass saves a contactor and wiring in the cabinet; external bypass requires reserved space and budget.

Q4: Can I still buy a Schneider ATS48? ATS48 was discontinued on 2023-07-12 (official datasheet), replaced by Altistart 480 (ATS480). For legacy replacement, evaluate ATS480 specifications and any cabinet modification required; for new projects, specify ATS480 directly.

Q5: Does an ABB PSR need additional protection? Yes. The ABB PSR body has no electronic motor overload protection; the datasheet pairs it with external thermal overload relays (TF42/TF65/TF96/TF140DU), while short-circuit and overload protection is provided by a manual motor starter or gG fuses.

Q6: How do I select a soft starter for heavy-duty starting (conveyor/crusher)? Select by duty class, not by the motor's nominal power. Siemens 3RW52 offers trip classes per IEC 60947-4-2 — CLASS 10A/10E/20E (use 20E for heavy duty); Schneider ATS48 selections use utilization category AC-53A and heavy-duty power points. Also verify the starts-per-hour limit.

Q7: Are soft starters suitable for frequent starting? No. Soft starters have starting capability limits (e.g. ABB PSR: 4 × Ie / 6 s, with a starts-per-hour table in the datasheet). High-cycle starting, jogging, or precise position control calls for a VFD.


Wishing you smooth procurement!
By: Shanghai Fradwell Industrial Automation Co., Ltd
— Your Sourcing Advisor for Chinese Automation

Shanghai Fradwell Industrial Automation Co., Ltd is a leading global supplier of high-performance industrial automation solutions, dedicated to connecting global buyers with high-quality Chinese automation solutions.

Product Categories:
PLC & Controllers

Siemens, Mitsubishi, Omron, Schneider, Delta, Xinje, Inovance, and other Chinese brands

HMI & Touch Screens

WEINVIEW, Kinco, MCGS, industrial panel PCs

Drives & Motors

Inverters, servo drives, stepper systems, gear motors

Sensors & Switches

Photoelectric switches, proximity switches, pressure sensors, temperature sensors, limit switches

Power Supplies & Relays

Switching power supplies, solid-state relays, contactors, circuit breakers

Pneumatic Components

Cylinders, solenoid valves, air treatment units

Core Services:
  • Multi-Brand Integration: One order, one shipment, zero hassle.
  • Technical Advisory: Pre-sales consulting by experienced automation engineers.
  • Guaranteed Authenticity: Strict quality control and reliable lead times (3-7 days).
Contact Us

Website: https://www.industrial-automationcontrol.com/

Email: cnsales@fradwell.com

WhatsApp/WeChat: +8617717562982

Send us your BOM (Bill of Materials) – we will reply with a competitive quote within 24 hours!Our technical team is ready to assist. Contact us today for a free consultation!